What is IEC 62271?
IEC 62271 is published under the general title High-voltage switchgear and controlgear. IEC technical committee 17 and its subcommittees maintain it. In this series, high voltage means a rated voltage above 1 kV, so the equipment many engineers call medium-voltage switchgear sits inside it.
The series has a common part and many product parts. Part 1, Common specifications for alternating current switchgear and controlgear, sets the shared rules for ratings, design, type tests and routine tests. A product part is read together with Part 1. Where the product part is more specific, it governs for that product.
Which parts of IEC 62271 does a tender name?
Broadly, parts numbered in the 100s deal with switching devices and parts in the 200s with assemblies. The table gives the parts that turn up most often in tenders, by subject. The series has many more, including technical reports and specifications. The IEC website has the current list and editions.
| Part | Subject | Typical tender question |
|---|---|---|
| IEC 62271-1 | Common specifications for AC switchgear and controlgear | Which edition the product parts in the offer were tested with |
| IEC 62271-100 | AC circuit-breakers | Ratings and the making and breaking duties the type tests cover |
| IEC 62271-102 | AC disconnectors and earthing switches | Ratings and classes of the earthing switch offered |
| IEC 62271-103 | Switches for rated voltages above 1 kV up to and including 52 kV | Whether a switch or a circuit-breaker is wanted in each functional unit |
| IEC 62271-105 | AC switch-fuse combinations | Transformer protection panels in ring main units |
| IEC 62271-106 | AC contactors, contactor-based controllers and motor-starters | Motor feeder panels |
| IEC 62271-200 | AC metal-enclosed switchgear and controlgear above 1 kV and up to and including 52 kV | Internal arc classification, service continuity category and the type tests for the assembly |
| IEC 62271-201 | AC solid-insulation enclosed switchgear and controlgear above 1 kV and up to and including 52 kV | Whether the offered panel belongs here and not under Part 200 |
| IEC 62271-202 | High-voltage/low-voltage prefabricated substations | The enclosure, transformer and both switchgear sections supplied as one tested unit |
| IEC 62271-203 | Gas-insulated metal-enclosed switchgear for rated voltages above 52 kV | Transmission-voltage gas-insulated substations |
Parts are revised separately. The current Part 200 is the third edition, published in 2021, and it was aligned with the 2017 edition of Part 1. A tender written from an older template may still cite earlier editions. Your type test reports state the edition they were made to, so compare the two and declare any difference.
Type tests and routine tests in IEC 62271
Each product part has a type test clause and a routine test clause. Type tests are made on representative equipment to prove the design and its ratings. Routine tests are made on what is actually delivered, to find faults in material or assembly. The table shows the headings Part 200 uses for a metal-enclosed assembly. It names the tests only. The procedures, test values and acceptance criteria are in the standard.
| Type tests include | Routine tests include |
|---|---|
| Dielectric tests | Dielectric test on the main circuit |
| Resistance measurement and continuous current tests | Measurement of the resistance of the main circuit |
| Short-time withstand current and peak withstand current tests | Tests on auxiliary and control circuits |
| Verification of the protection provided by the enclosure | Design and visual checks |
| Tightness tests and pressure withstand tests for gas-filled compartments | Tightness test and pressure tests of gas-filled compartments |
| Verification of making and breaking capacities | Mechanical operation tests |
| Mechanical operation tests | Partial discharge measurement |
| Internal arc test | Tests after erection on site, where they apply |
Not every heading applies to every assembly, and some are subject to agreement. A tender often adds to both lists. It may ask for type test reports from an independent laboratory, set a maximum age for them, or ask for a routine test to be witnessed. See type test vs routine test for the general idea across transformers and switchgear.
What is internal arc classification?
An internal arc is a fault inside the enclosure that releases hot gas and pressure. Part 200 lets a manufacturer assign an internal arc classification, written IAC, to an assembly that has passed the internal arc test set out in the standard. The classification is about protecting people near the assembly in normal operating condition. It is not a statement that the equipment survives the fault.
The designation has three elements, and a tender should give all three.
- Type of accessibility. Type A is restricted to authorised personnel. Type B is unrestricted and includes the general public.
- Classified sides. For types A and B the letters F, L and R mark the front, lateral and rear sides that met the test criteria.
- Arc fault current and duration. The designation ends with the tested current and time.
The test is made in a room simulation, and the arrangement tested matters. Ceiling height, distance to walls and any gas exhaust duct are part of what was proved. When a tender gives switchroom dimensions, check them against the installation conditions stated in your test report and manual. Older editions and older data sheets also show a type C, for pole-mounted equipment out of reach. Internal arc testing of pole-mounted switchgear was taken out of the 2021 edition and now has its own part, IEC 62271-214.
Two other classifications the tender may quote
Part 200 also has a loss of service continuity category, written LSC1, LSC2, LSC2A or LSC2B. It describes which other compartments and functional units can stay energised while one compartment is open. Partition class PM or PI says whether partitions and shutters are metal or insulating. A tender line can combine all of these with the IAC designation in one string, so check each element against your type test evidence.
What about low-voltage switchgear and IEEE?
Low-voltage assemblies are not covered by IEC 62271. They fall under IEC 61439, where Part 1 gives general rules and Part 2 covers power switchgear and controlgear assemblies. That series uses different words for the same idea. Design verification proves the design, by test or by one of the other routes the standard allows for each characteristic. Routine verification is made on every assembly built. It replaced the older IEC 60439 terms type-tested and partially type-tested assembly, which still appear in tender templates.
Buyers working to North American practice cite the IEEE C37 series for switchgear in place of IEC 62271. Ratings and test duties are defined differently, so a type test report to one family does not automatically answer a requirement written to the other. Raise it as a clarification.
How does OdysseyGPT help with an IEC 62271 tender?
Document Review checks the buyer's switchgear specification and schedules against your technical data sheets, catalogue ratings, type test report summaries and offer text. Each requirement gets a status and a quote from both sides. A rating string such as an IAC designation is compared as written, so a missing side letter or a different duration shows up as a difference for an engineer to judge.
Datasheet Comparison (beta) compares the buyer's panel schedule with yours, field by field. Deviation Register (beta) keeps one record of each deviation through the clarification rounds. After award, FAT Readiness Check (beta) reads the routine test procedure, ITP status and open items before a witnessed test, and MRB Readiness Check (beta) compares the dossier folder with the buyer's index.
What it does not do
OdysseyGPT does not test switchgear and does not decide whether a type-tested arrangement covers the panel you offer. It does not read single-line diagrams, panel layouts or switchroom drawings, so a requirement shown only there is not checked. It carries no copy of IEC 62271. Engineers confirm every row.
What to check in a switchgear tender against IEC 62271
This is a reading list for the tender. It is not a summary of what the standard requires. Part 200 itself has an informative clause on the information to give with enquiries, tenders and orders, which is worth reading beside it.
| Check | Look in the tender for | Look in your documents for |
|---|---|---|
| Parts and editions | Each part of IEC 62271 named, with its year, and any national or utility standard beside it | The edition on each type test report |
| Which product part applies | Whether the panel described is metal-enclosed, solid-insulation enclosed, gas-insulated or a prefabricated substation | The part your product is declared to |
| Service conditions | Indoor or outdoor, altitude, temperature and other conditions the standard treats as special | The conditions your ratings assume |
| Rated values | Rated voltage, insulation level, frequency, continuous current, short-time and peak withstand currents and duration | The same values on the nameplate data and data sheet, for busbars and each feeder |
| Switching devices | Device type in each functional unit and the part of the series it must meet | Type test evidence for each device as installed in the panel |
| Internal arc classification | Accessibility type, classified sides, arc current and duration, and the switchroom dimensions | The IAC designation and the installation conditions in the test report |
| Service continuity and partitions | The LSC category and partition class asked for | The category and class declared for each functional unit |
| Enclosure and interlocks | Degree of protection, earthing arrangements, interlocks and locking facilities | The matching statements in your specification and manual |
| Gas and tightness | The insulating or switching medium accepted, and any limit on gas type | The medium used and the tightness data you declare |
| Type test evidence | Which reports are wanted, from which kind of laboratory and how recent | A list of reports with design, date, laboratory and tests covered |
| Routine tests and witnessing | Additions to the routine tests, witness rights and notice period | Your routine test procedure, report format and ITP |
| Auxiliary and control equipment | Auxiliary supply voltages, protection relays, metering and communication interfaces | The schedule of secondary equipment in the offer |
| Site work | Tests after erection, commissioning and training | What the offer includes on site |
| Documents | Drawings for approval, manuals, test reports and the final dossier index | Your standard document list and any gaps |