Who each standard is for
| IEC 61508 | IEC 61511 | |
|---|---|---|
| Scope | Functional safety of electrical, electronic and programmable electronic safety-related systems, in any sector | Safety instrumented systems for the process industry sector |
| Main users | Device and system manufacturers | End users, designers and system integrators |
| Structure | Seven parts: general, hardware, software, definitions, and guidance parts | Three parts: requirements, guidance on applying them, and guidance on setting the required SIL |
| In a tender | The basis for the maker's failure data, safety manual and assessment | The basis for the buyer's SIL targets and device selection rules |
What SIL means for a valve, actuator or instrument
A safety integrity level, SIL 1 to SIL 4, states how much risk reduction a safety instrumented function must provide. The function includes sensors, a logic solver and final elements. A single device is not SIL rated on its own; it is suitable for use in a function up to a given SIL, based on its failure rates, hardware fault tolerance and systematic capability. When a tender asks for a SIL 3 valve, read it as a request for that evidence.
What to check in your offer against a SIL requirement
Any gap becomes a row in your technical deviation list.
| Item | Check against | Typical deviation source |
|---|---|---|
| Target SIL and function | Specification, data sheet or safety requirements specification | Target SIL stated without the function or safe state |
| Evidence of suitability | Certificate or assessment report | Covers a different model, option or firmware |
| Systematic capability | Target SIL | SC lower than the target SIL |
| Failure data | FMEDA or assessment report | Data covers the actuator only, not the full assembly |
| Proof test | Buyer's test interval and procedure | Different interval or coverage assumed |
| Safe state and stroke time | Cause and effect, data sheet | Fail action or stroke time does not match |
| Partial stroke testing | Specification | No partial-stroke option offered |
| Documents | VDRL | Safety manual or proof test procedure not listed |
Where OdysseyGPT fits
Functional safety requirements are often split between the specification, the data sheets, the safety requirements specification and the VDRL. OdysseyGPT reads the whole package, lists each requirement with a quote and page, and checks it against your own safety manuals and datasheets. It does not calculate PFD or certify devices. See OdysseyGPT for manufacturing.