What is ISO 14644?
ISO 14644, Cleanrooms and associated controlled environments, is a series of international standards. It deals with rooms and zones where the concentration of airborne particles is controlled. Electronics, pharmaceutical, medical device, aerospace and hospital projects all use it. It is written around the room and the people who design, build, test and run it. It is not a product standard for an air handling unit or a filter.
That is why it reaches an equipment maker second-hand. The cleanroom designer sets a class for each room. The specification for each piece of equipment then carries the requirements the designer derived from it: filter classes, air flows, leakage, surfaces, test ports and documents.
The parts a specification cites most often
| Part | Subject | What it means for an equipment supplier |
|---|---|---|
| Part 1 | Classification of air cleanliness by particle concentration. It defines the ISO classes and how a room is measured against one with a particle counter | The class named in your specification comes from here. It applies to the room, zone or separative device, not to your unit alone |
| Part 2 | Monitoring to provide evidence that a cleanroom keeps performing to its class, through a monitoring plan based on risk | The user may ask for sampling points, sensor provisions or data outputs on your equipment |
| Part 3 | Test methods for cleanrooms and clean zones, such as air flow, pressure difference, installed filter system leakage, airflow direction and recovery tests | Filter housings and fan filter units need to be testable in place. The specification may name which tests are yours |
| Part 4 | Design, construction and start-up of a cleanroom, from requirements through to handover, for new and modified installations | It frames the documents and checks a cleanroom contractor passes down to its suppliers |
The series has further parts. Part 5 covers operations and Part 7 covers separative devices such as isolators and clean air hoods. Others deal with subjects such as surface and chemical cleanliness. Check which parts and which editions your specification names. Editions move on: Part 1 was reissued in 2015, Part 3 in 2019 and Part 4 in 2022, for example, and older specifications often cite earlier ones. Confirm the current edition of each part in the ISO catalogue.
What is an ISO class?
Part 1 sets out nine classes, ISO Class 1 to ISO Class 9. A lower number means cleaner air. Each class sets a maximum concentration of particles at and above stated sizes. The standard considers threshold sizes from 0.1 to 5 micrometres for classification. We do not reproduce the limits table here. Take the figures from the edition your contract names.
A class number alone is an incomplete statement. A full one gives three things.
- The ISO class number.
- The occupancy state: as-built, with the room complete but no process equipment or people; at-rest, with equipment installed and running but no people; or operational, with the process running and staff present.
- The particle size or sizes the class was assessed at.
The state matters commercially. A room that meets its class at rest may not meet it in operation, and the difference depends on the process and the people as much as on the air system. If a specification asks you to guarantee a class, check which state it means. The glossary entry on cleanroom classification goes into this.
How ISO classes relate to EU GMP grades
Makers of sterile medicines in the EU follow Annex 1 of the EU GMP guide. Annex 1 does not use ISO class numbers as its own system. It defines four grades, A to D, where grade A is the critical zone. For each grade it gives its own table of particle limits, with separate columns for the at rest and in operation states, and it adds limits for microbial contamination, which ISO 14644-1 does not cover.
| ISO 14644-1 | EU GMP Annex 1 | |
|---|---|---|
| Who uses it | Any industry with a cleanroom | Manufacturers of sterile medicinal products |
| Scale | ISO Class 1 to 9 | Grades A, B, C and D |
| States | As-built, at-rest and operational | At rest and in operation |
| What is limited | Airborne particle concentration | Airborne particles and microbial contamination |
| How the two connect | Supplies the classification method | Refers to ISO 14644-1 for sampling locations and to the ISO 14644 series for qualification |
People often describe a grade by an ISO class. Treat that as shorthand. If a specification gives both a grade and an ISO class, the grade's own limits in Annex 1 govern for a GMP project, and the two should be checked for agreement. Annex 1 also treats classification as one part of cleanroom qualification, alongside tests such as installed filter leakage, air flow, pressure difference, airflow visualisation and recovery, and it sets maximum intervals for requalification. Pharmaceutical projects add documents of their own. See pharmaceutical equipment manufacturers.
What an equipment supplier is asked to show
No air handling unit, fan filter unit or wall panel has an ISO class by itself. The class is measured in the finished room by whoever is contracted to test it. What the supplier provides is equipment that makes the class reachable and evidence that the equipment is what the designer assumed.
- Air handling units: air flow and pressure at the scheduled duty point, filter stages and classes, casing leakage class, internal surfaces that can be cleaned, and the points an air handling unit specification adds for clean applications.
- Fan filter units and terminal filter housings: the filter class, an individual test report for each high-efficiency filter, face velocity data, and provision for testing the installed filter for leaks.
- Filters: the class and the standard it is stated to, such as ISO 16890 for general ventilation stages and EN 1822 for high-efficiency stages.
- Wall and ceiling panels, doors and pass-throughs: surface materials and finish, joint and seal details, and cleaning agents the surfaces tolerate.
- Instruments supplied with the equipment: range, accuracy and a calibration certificate for each.
- Documents: installation and operating instructions, drawings, material and filter certificates, factory test reports and the papers the user needs for installation and operational qualification.
These go to the customer as part of the HVAC submittal and, later, the handover file. For the qualification stages, see IQ, OQ and PQ.
What to check in a cleanroom equipment specification against ISO 14644
| Check | Why it matters |
|---|---|
| Which parts of ISO 14644 are named, and which editions | Reused specifications cite superseded editions, and the test methods part has changed over time |
| The class of each room your equipment serves, with its occupancy state and particle sizes | A class with no state cannot be priced or guaranteed |
| Whether a GMP grade is given as well, and whether it agrees with the ISO class | The grade brings in-operation and microbial limits that the ISO class does not |
| Whether you are asked to guarantee the room class or only equipment performance | Room class depends on the envelope, the process and the people, which you may not control |
| Filter class at each stage and the standard it is stated to | Classes from different filter standards are not interchangeable labels |
| Evidence for high-efficiency filters: individual test reports and who tests the installed filter | The installed leak test is site work with its own equipment and cost |
| Test ports, access and clearances needed for in-place tests | A housing that cannot be tested in place fails at qualification, not at the factory |
| Casing and ductwork leakage classes | Leakage downstream of the final filter stage undermines the room |
| Surface finish, materials and resistance to the user's cleaning and disinfection agents | These are judged at design review and are costly to change later |
| Which Part 3 tests are in your scope, at the factory or on site | Air flow, pressure, recovery and filter leak tests may sit with you, the contractor or a test house |
| Monitoring provisions: particle counter ports, pressure sensors, data outputs | The user's monitoring plan may need them built in |
| Qualification documents wanted, their format and who approves them | Protocol writing and review cycles take engineering time |
Write each gap as a row in your technical deviation list. A layout for the document set is on the HVAC submittal checklist template page. OdysseyGPT's Document Review checks the specification against your product data, test report summaries and offer text, and drafts the compliance matrix and deviation list with a quote for each row. Customer Specification Review (beta) lists the obligations in the specification, one line each. After award, the Calibration Validity Check (beta) matches each instrument on a test report to its certificate.
What OdysseyGPT does not do
OdysseyGPT reads documents. It does not classify a cleanroom, count particles, test a filter or judge whether a room will reach its class. It does not read layout or airflow drawings, and it holds no copy of ISO 14644. Your engineers decide every status. See HVAC and cleanroom equipment manufacturers.