Air Handling Unit Specification

The written section and schedule in which a consulting engineer sets what an air handling unit must do and how it must be built: duty, casing, components, sound, controls, tests and documents.

Last reviewed by the OdysseyGPT team

What it is

An air handling unit specification is the engineer's written section and equipment schedule for the units on a project. The schedule gives each unit's air flows, pressures, coil duties and filter classes. The section sets casing construction and classes, components, sound limits, controls, tests and documents, and usually cites EN 1886 and EN 13053 or AHRI and ASHRAE standards.

Key Takeaways

  • Read the schedule row and the written section together. Neither is complete alone.
  • Casing classes usually refer to EN 1886. Unit ratings refer to EN 13053 or AHRI standards.
  • Check whether casing evidence is wanted from a model box or from the delivered unit.
  • A named basis of design puts the burden of showing differences on the alternative maker.

Why it matters

An air handling unit specification is the engineer's statement of what each unit on a project must achieve and how it is to be constructed. It comes in two parts that must be read together. The schedule gives the numbers for each tag: supply and return air flows, external static pressure, coil duties with entering and leaving air and fluid conditions, filter classes, humidifier and heat recovery duties, motor data and electrical supply. The written section gives everything that applies to all units. That covers casing construction and panel thickness, the classes wanted for casing strength, air leakage, filter bypass leakage, thermal transmittance and thermal bridging, fan type and drive, coil materials, drain pans, dampers, filters and frames, access doors and lighting, sound limits, and the split between factory-fitted and site-fitted controls. In Europe and many export markets the casing classes refer to EN 1886 and unit ratings to EN 13053, often with a requirement for Eurovent certification. North American sections cite AHRI rating standards and ASHRAE standards for energy, ventilation and filtration. Units for hospitals and cleanrooms add clauses on hygienic construction, cleanable surfaces and higher filter classes. The section closes with factory tests, the submittal contents, operation and maintenance manuals, spares and warranty. Many sections name a basis-of-design maker and allow an approved equal. The classes and limits themselves are in the standards. This page does not reproduce them, and class names can change between editions, so check the edition your contract cites.

How OdysseyGPT uses it

Customer Specification Review (beta) lists the obligations in the section, one line each with its clause, so nothing in the text is left out of the offer. Document Review then checks the section and schedule against your technical data and selection printouts and quotes both sides on every row. OdysseyGPT does not size the unit, calculate its performance or read the plant room drawings, and it holds no copy of the standards cited. Engineers decide each status.

Evaluation questions

Which air handling unit specification clauses are most often missed in an offer?

The ones with no line in the schedule: casing classes and how they must be proven, casing radiated sound, access side and service clearances, controls scope, factory tests and witness rights. They sit in the written section, so a selection that matches the schedule can still miss them.

Frequently asked questions

What does EN 1886 cover in an air handling unit specification?

The mechanical performance of the casing. It gives test methods and classes for casing strength, air leakage, filter bypass leakage, thermal transmittance, thermal bridging and acoustic insulation. A specification picks the class it wants for each.

What is a model box?

A standard test enclosure built with the maker's casing construction and used to establish casing classes. A specification may accept model box results or ask for a test on the unit delivered. The two are not the same evidence.

What does basis of design mean for an air handling unit?

It is the maker and model the engineer used to lay out the plant room, ductwork and services. Other makers may be allowed as equals, but they are expected to show where their unit differs in size, weight, connections and electrical load.

References

EN 1886:2025 Ventilation for buildings. Air handling units. Mechanical performance

Estonian Centre for Standardisation and Accreditation (catalogue entry)

Paid standard. Catalogue entry used for the title and scope.

Visit source

EN 13053:2019 Ventilation for buildings. Air handling units. Rating and performance for units, components and sections

Estonian Centre for Standardisation and Accreditation (catalogue entry)

Paid standard. Catalogue entry used for the title and scope.

Visit source

Eurovent Certified Performance: Air Handling Units

Eurovent Certita Certification

Programme scope and the certified casing and performance characteristics.

Visit source

AHRI Certification

Air-Conditioning, Heating, and Refrigeration Institute

The certification programme and the directory of certified product performance.

Visit source